Standard or regulation
Emergency Communication Requirements for Buildings
An overview of the requirements that govern emergency communication circuits in buildings — elevator emergency phones, area-of-refuge stations, emergency call boxes, and alarm reporting paths — which are established across several codes rather than in one document.
- Issuing organization
- Multiple — NFPA, ASME, state and local authorities
- Edition
- Varies by code and by the edition each jurisdiction has adopted.
- Jurisdictions
- United States; Canada; varies by jurisdiction
Scope
Applies wherever a building contains a communication path relied on in an emergency. Requirements are distributed across NFPA codes, ASME A17.1/CSA B44 for elevators, building and fire codes, accessibility requirements, and state or local amendments.
Key considerations
No single governing document
Because requirements are spread across several codes, a migration touching emergency circuits usually engages more than one authority. Identify which codes apply to each circuit type before planning.
Reaching a responder, not just placing a call
Most requirements specify that a call reaches personnel able to respond. Verifying a replacement means testing the whole path to the responder, not just confirming dial tone.
Power and supervision recur
Across these codes, backup power and detection of path failure appear repeatedly. Replacement equipment with integrated battery and remote supervision addresses recurring requirements rather than one-off ones.
Accessibility overlaps
Accessibility requirements can affect emergency communication equipment, including two-way communication features. Coordinate with accessibility review where relevant.
The recurring theme across every one of these codes is the same pair: the path must work when power does not, and its failure must be detectable.
Frequently asked questions
Primarily ASME A17.1/CSA B44 as adopted by the jurisdiction, with building and fire codes and accessibility requirements potentially also applying.
Typically yes, or at minimum acceptance on inspection. Because these circuits are code-governed, engaging the AHJ before migrating is far cheaper than remediating a rejected installation.
Testing only for dial tone. A path can present dial tone and still fail to deliver a usable call to a responder, or fail to be supervised as the code requires.
Related to this standard
Products
Solutions
Definitions
Topics
Related standards
Official sources
- NFPA 72: National Fire Alarm and Signaling Code (opens in a new tab) — National Fire Protection Association
- ASME A17.1/CSA B44 Safety Code for Elevators and Escalators (opens in a new tab) — American Society of Mechanical Engineers
Last reviewed .